Radon and its decay products in an air-conditioned auditorium in correlation with indoor air parameters
PBN-AR
Instytucja
Wydział Inżynierii Środowiska (Politechnika Lubelska)
Informacje podstawowe
Główny język publikacji
angielski
Czasopismo
INDOOR AND BUILT ENVIRONMENT
ISSN
1420-326X
EISSN
Wydawca
DOI
URL
Rok publikacji
2016
Numer zeszytu
0
Strony od-do
1-10
Numer tomu
0
Identyfikator DOI
Liczba arkuszy
Autorzy
(liczba autorów: 5)
Pozostali autorzy
+ 3
Open access
Tryb otwartego dostępu
Otwarte czasopismo
Wersja tekstu w otwartym dostępie
Wersja opublikowana
Licencja otwartego dostępu
Inna
Czas opublikowania w otwartym dostępie
Razem z publikacją
Data udostępnienia w sposób otwarty
Streszczenia
Język
EN
Treść
The measurements of radon and its attached decay product activity concentrations were carried out in an occupied and unoccupied auditorium during three air-conditioning modes i.e. air-conditioning system switched off (air-conditioning off), air-conditioning system switched off during the night and switched on during the day (air-conditioning on/off) and air-conditioning system switched on (air-conditioning on). Higher average concentrations of radon and its decay products were recorded in the auditorium when the air-conditioning system was switched off. The average particle mass and CO2 concentrations and indoor air thermal parameters were elevated during the air-conditioning on/off mode. A statistically significant (p < 0.001) positive correlation between the decay product concentrations and the particle number and average particle mass concentrations has been observed in the air-conditioning off mode (r = 0.55 and r = 0.68) and in the air-conditioning on/off mode (r = 0.54 and r = 0.62, respectively). A significant negative correlation has been observed between the decay product concentrations and the indoor air temperature and CO2 concentrations in the air-conditioning off mode (r = −0.86 and r = −0.47, respectively). The obtained results confirmed the impact of the air-conditioning system operation on the decrease of health risks related to the presence of radon and its decay products in air conditioned premises.
Inne
System-identifier
20960
CrossrefMetadata from Crossref logo
Cytowania
Liczba prac cytujących tę pracę
Brak danych
Referencje
Liczba prac cytowanych przez tę pracę
Brak danych